3-46 Protection

Functions

865-UM001A-EN-P – July 2009

Inverse Time Setting Error Signal

The inverse time setting error signal will become active, if
interpolation with the given parameters is not possible. See Chapter 2
for more details.

Limitations

The minimum definite time delay start latest, when the measured
value is twenty times the setting. However, there are limitations at
high setting values due to the measurement range. See Chapter 2 for
more details.

Programmable Inverse Time Curves

The [current, time] curve points are programmed only using
SetPointPS PC program. There are some rules for defining the curve
points:

Configuration must begin from the topmost line

Line order must be as follows: the smallest current (longest
operation time) on the top and the largest current (shortest
operation time) on the bottom

All unused lines (on the bottom) should be filled with [1.00
0.00s]

Device must be rebooted to initialize the settings.

Here is an example configuration of curve points:

Table 3.26 – Curve Point Configurations

Point

Current I/I

pick-up

Operation delay

1 1.00

10.00

s

2 2.00

6.50

s

3 5.00

4.00

s

4 10.00

3.00

s

5 20.00

2.00

s

6 40.00

1.00

s

7 1.00

0.00

s

8 1.00

0.00

s

9 1.00

0.00

s

10 1.00

0.00

s

11 1.00

0.00

s

12 1.00

0.00

s

13 1.00

0.00

s

14 1.00

0.00

s

15 1.00

0.00

s

16 1.00

0.00

s