Tests and environmental conditions, Disturbance tests, Test voltages – Rockwell Automation 865 Differential Protection Relay User Manual

Page 174: Mechanical tests, Environmental conditions

Advertising
background image



10-4 Technical

Data

865-UM001A-EN-P – July 2009

Table 10.9 – Disturbance Tests

Emission (EN 50081-1)

- Conducted (EN 55022B)

0.15 - 30 MHz

- Emitted (CISPR 11)

30 - 1 000 MHz

Immunity (EN 50082-2)

- Static discharge (ESD)

EN 61000-4-2, class III

6 kV contact discharge

8 kV air discharge

- Fast transients (EFT)

EN 61000-4-4, class III

2 kV, 5/50 ns, 5 kHz, +/-

- Surge

EN 61000-4-5, class III

2 kV, 1.2/50 s, common mode

1 kV, 1.2/50 s, differential mode

- Conducted HF field

EN 61000-4-6

0.15 - 80 MHz, 10 V

- Emitted HF field

EN 61000-4-3

80 - 1000 MHz, 10 V/m

- GSM test

ENV 50204

900 MHz, 10 V/m, pulse modulated


Table 10.10 – Test Voltages

Insulation test voltage (IEC 60255-5)
Class III

2 kV, 50 Hz, 1 min

Surge voltage (IEC 60255-5)
Class III

5 kV, 1.2/50 s, 0.5 J


Table 10.11 – Mechanical Tests

Vibration (IEC 60255-21-1)

10 ... 60 Hz, amplitude ±0.035 mm

Class I

60 ... 150 Hz, acceleration 0.5g

sweep rate 1 octave/min

20 periods in X-, Y- and Z axis direction

Shock (IEC 60255-21-1)

half sine, acceleration 5 g, duration 11 ms

Class I

3 shocks in X-, Y- and Z axis direction


Table 10.12 – Environmental Conditions

Operating temperature

-10 to +55 C

Transport and storage temperature

-40 to +70 C

Relative humidity

< 75% (1 year, average value)

< 90% (30 days per year, no condensation permitted)

Tests and Environmental
Conditions