Non-directional current protection – Rockwell Automation 865 Differential Protection Relay User Manual

Page 176

Advertising
background image



10-6 Technical

Data

865-UM001A-EN-P – July 2009


Non-directional

Current

Protection

Table 10.17 – Overcurrent Stage I>, I’> (50/51)

Pick-up current

0.10 – 5.00 x I

mode

Definite time function:

DT

- Operating time

0.08

– 300.00 s (step 0.02 s)

IDMT function:

- Delay curve family

(DT), IEC, IEEE, RI Prg

- Curve type

EI, VI, NI, LTI, MI…depends on the family

- Time multiplier k

0.05 – 20.0, except
0.50 – 20.0 for RXIDG, IEEE and IEEE2

Start time

Typically 60 ms

Reset time

<95 ms

Retardation time

<50 ms

Reset ratio

0.97

Transient over-reach, any

τ

<10 %

Inaccuracy:
- Starting

±3% of the set value

- Operating time at definite time function

±1% or ±30 ms

- Operating time at IDMT function

±5% or at least ±30 ms

EI = Extremely Inverse, NI = Normal Inverse, VI = Very Inverse, LTI = Long Time Inverse

MI= Moderately Inverse

This is the instantaneous time i.e. the minimum total operational time including the fault

detection time and operation time of the trip contacts.

Table 10.18 – Overcurrent Stages I>> and I’>> (50/51)

Pick-up current

0.10 – 20.00 x I

mode

(I>>)

Definite time function:


0.04

– 300.00 s (step 0.01 s)

- Operating time

Start time

Typically 60 ms

Reset time

<95 ms

Retardation time

<50 ms

Reset ratio

0.97

Transient over-reach, any

τ

<10 %

Inaccuracy:
- Starting

±3% of the set value

- Operation time

±1% or ±25 ms

This is the instantaneous time i.e. the minimum total operational time including the fault

detection time and operation time of the trip contacts.