Recorded values of the latest eight faults – Rockwell Automation 865 Differential Protection Relay User Manual

Page 74

Advertising
background image



3-30 Protection

Functions

865-UM001A-EN-P – July 2009

Table 3.17 – Parameters of Arc Protection Stages Arcl>, Arcl’>, Arcl

01

A,

Arcl

02

> (50 ARC / 50N ARC) (cont.)

Parameter

Value

Unit

Description

Note

ArcI>
ArcI’>
ArcIo1>
ArcIo2>

pu

pu
pu
pu

Pick up setting xI

N

Pick up setting xI’

N

Pick up setting xI

01N

Pick up setting xI

02N

Set

ArcIn


S1
S2
S1/S2
BI
S1/BI
S2/BI
S1/S2/BI

Light indication source selection
No sensor selected
Sensor 1 at terminals X6:4-5
Sensor 2 at terminals X6:6-7

Terminals X6:1-3

Set

Delayed light signal output

Ldly

s

Delay for delayed light output signal

Set

LdlyCn


S1
S2
S1/S2
BI
S1/BI
S2/BI
S1/S2/BI

Light indication source selection
No sensor selected
Sensor 1 at terminals X6:4-5
Sensor 2 at terminals X6:6-7

Terminals X6:1-3

Set

For details of setting ranges see “Protection Stages” in Chapter 10.

Set = An editable parameter (password needed)

C = Can be cleared to zero

F = Editable when force flag is on

Recorded Values of the Latest Eight Faults

Detailed information is available on the eight latest faults: Time
stamp, fault type, fault value, load current before the fault and
elapsed delay.

Table 3.18 – Recorded Values of the Arc Protection Stages Arcl>, Arcl’>,
Arcl

01

A, Arcl

02

> (50 ARC / 50N ARC)

Parameter

Value

Unit

Description

yyyy-mm-dd

Time stamp of the recording, date

hh:mm:ss.ms

Time stamp, time of day

Type

pu

Fault type value. Only for ArcI> stage.

Flt

pu

Fault

value

Load

pu

Pre fault current. Only for ArcI> stage.

EDly

%

Elapsed time of the operating time setting.
100% = trip