Operation indicators – Rockwell Automation 865 Differential Protection Relay User Manual

Page 16

Advertising
background image



2-4

Local Panel User Interface

865-UM001A-EN-P – July 2009

4.

Keys for selecting submenus [selecting a digit in a numerical

value] (LEFT/RIGHT)

5.

Additional information key (INFO)

NOTE: The term, which is used for the buttons in this manual,

is inside the rounded brackets.


Operation

Indicators


The relay is provided with eight LED indicators:

Power

Error
Com

Alarm
Trip
A
B
C

Figure 2.5 – Operation Indicators of the Relay

Table 2.1 – Operation Indicators

LED indicator

Meaning

Measure/ Remarks

Power LED lit

The power has been switched on

Normal operation state

Error LED lit

Internal fault, operates in parallel with
the self supervision output relay

The relay attempts to reboot
[REBOOT]. If the error LED
remains lit, call for maintenance.

Com LED lit or flashing

The serial bus is in use and
transferring information

Normal operation state

Alarm LED lit

One or several signals of the output
relay matrix have been assigned to
output LA and the output has been
activated by one of the signals. (For
more information about output matrix,
please see page 2-24).

The LED is switched off when the
signal that caused output Al to
activate, e.g. the START signal, is
reset. The resetting depends on the
type of configuration, connected or
latched.

Trip LED lit

One or several signals of the output
relay matrix have been assigned to
output Tr, and the output has been
activated by one of the signals. (For
more information about output relay
configuration, see “Configuring Digital
Outputs DO” on page 2-24).

The LED is switched off when the
signal that caused output Tr to
activate, e.g. the TRIP signal, is
reset. The resetting depends on the
type of configuration, connected or
latched.

A- C LED lit

Application-related status indicators.

Configurable