Local Panel User Interface

2-29

865-UM001A-EN-P – July 2009

PROFIBUS

Only one instance of this protocol is possible.

[Mode]

Bit rate [bit/s]. Use 2400 bps. This parameter is the bit rate
between the main CPU and the Profibus ASIC. The actual
Profibus bit rate is automatically set by the Profibus master and
can be up to 12 Mbit/s.

Event numbering style [Emode].

Size of the Profibus Tx buffer [InBuf].

Size of the Profibus Rx buffer [OutBuf].
When configuring the Profibus master system, the length of
these buffers are needed. The size of the both buffers is set
indirectly when configuring the data items for Profibus.

Address for this slave device [Addr]. This address has to be
unique within the system.

Profibus converter type [Conv]. If the shown type is a dash “-“,
either Profibus protocol has not been selected or the device has
not restarted after protocol change or there is a communication
problem between the main CPU and the Profibus ASIC.

For details see the technical description part of the manual.

DNP3

Only one instance of this protocol is possible.

Bit rate [bit/s]. Default is "9600".

[Parity].

Addres for this device [SlvAddr]. This address has to be unique
within the system.

Master's addres [MstrAddr].

For further details see the technical description part of the manual.

TCP/IP

These TCP/IP parameters are used by the ethernet interface module.
For changing the nnn.nnn.nnn.nnn style parameter values,
SetPointPS is recommended.

IP address [IpAddr].

Net mask [NetMsk].

Gateway [Gatew].

Name server [NameSw].

Network time protocol (NTP) server [NTPSvr].

Protocol port for IP [Port]. Default is 502.