Rockwell Automation 865 Differential Protection Relay User Manual

Page 81

Advertising
background image



Protection Functions

3-37

865-UM001A-EN-P – July 2009


Table 3.23 – Constants for IEC Inverse Delay Equation

Parameter

Delay type

A

B

NI Normal

inverse

0.14

0.02

EI Extremely

inverse

80

2

VI Very

inverse

13.5

1

LTI Long

time

inverse

120

1

Example for Delay type "Normal inverse (NI) ":

k

=

0.50

I

=

4 pu (constant current)

I

pickup

=

2

pu

A

= 0.14

B

= 0.02

0

.

5

1

2

4

14

.

0

50

.

0

02

.

0

=

=

t

The operation time in this example will be 5 seconds. The same
result can be read from Figure 3.16.


Figure 3.16 – IEC Normal Inverse Delay