Rockwell Automation 865 Differential Protection Relay User Manual

Page 64

Advertising
background image

3-20 Protection

Functions

865-UM001A-EN-P – July 2009

Table 3.11 – Parameters of the Undirectional Earth Fault Stage I

0

> (50N/51N)

(cont.)

Parameter

Value

Unit

Description

Note

Io
Io2
IoCalc
IoPeak
Io2Peak
I’oCalc

pu

The supervised value according the
parameter "Input" below.

Io>

A

Pick-up value scaled to primary value

Io>

pu

Pick-up setting relative to the parameter
"Input" and the corresponding CT value

Set

Curve

DT
IEC
IEEE
IEEE2
RI
PrgN

Delay curve family:
Definite time
Inverse time. See “Inverse Time
Operation”.



Set

Type

DT
NI
VI
EI
LTI
Parameters

Delay type.
Definite time
Inverse time. See “Inverse Time
Operation”, Table 3.23.



Set

t>

s

Definite operation time (for definite time
only)

Set

k>

Inverse delay multiplier (for inverse time
only)

Set

Input Io1

Io2
IoCalc
Io1Peak
Io2Peak
I’oCalc

X1-7&8. See Chapter 9.
X1-9&10
IL1 + IL2 + IL3
X1-7&8 peak mode
X1-9&10 peak mode
I’L1 + I’L2 + I’L3


Set

Intrmt

s

Intermittent

time

Set

Dly20x

s Delay

at

20xIset

Dly4x

s

Delay

at

4xIset

Dly2x

s

Delay

at

2xIset

Dly1x

s

Delay

at

1xIset

A, B, C, D,
E

User's constants for standard equations.
Type=Parameters. See “Inverse Time
Operation”.

Set

For details of setting ranges see “Protection Stages” in Chapter 10.

Set = An editable parameter (password needed)

C = Can be cleared to zero

F = Editable when force flag is on