Rockwell Automation 865 Differential Protection Relay User Manual

Page 40

Advertising
background image



2-28

Local Panel User Interface

865-UM001A-EN-P – July 2009

EXTENSION PORT X4 (pins 7, 8 and 5)

Communication protocol for extension port X4 [Protocol].

Message counter [Msg#]. This can be used to verify that the
device is receiving messages.

Communication error counter [Errors].

Communication time-out error counter [Tout].

Information of bit rate/data bits/parity/stop bits.
This value is not directly editable. Editing is done in the
appropriate protocol setting menus.

MODBUS

Modbus address for this slave device [Addr]. This address has to
be unique within the system.

Modbus bit rate [bit/s]. Default is "9600".

Parity [Parity]. Default is "Even".

For details see the technical description part of the manual.

EXTERNAL

I/O

protocol

This is a Modbus master protocol to communicate with the
extension I/O modules connected to the extension port. Only one
instance of this protocol is possible.

Bit rate [bit/s]. Default is "9600".

Parity [Parity]. Default is "Even".

For details see the technical description part of the manual.

SPA

BUS

Several instances of this protocol are possible.

SPABUS address for this device [Addr]. This address has to be
unique within the system.

Bit rate [bit/s]. Default is "9600".

Event numbering style [Emode]. Default is "Channel".

For details see the technical description part of the manual.

IEC

60870-5-103

Only one instance of this protocol is possible.

Address for this device [Addr]. This address has to be unique
within the system.

Bit rate [bit/s]. Default is "9600".

Minimum measurement response interval [MeasInt].

ASDU6 response time mode [SyncRe].

For details see the technical description part of the manual.

IEC 103 DISTURBANCE RECORDINGS

For details see the technical description part of the manual.

Configuration and
Parameter Setting
(cont.)