Example of a behavior of the thermal model, Initial temperature rise after restart, Alarm function – Rockwell Automation 865 Differential Protection Relay User Manual

Page 68

Advertising
background image



3-24 Protection

Functions

865-UM001A-EN-P – July 2009

k

Q

I

MAX70

I

MAX40

Q

AMB

(°C)

AmbientTemperatureCompensation

0.6

10 20 30 40 50 60 70 80

0.8

1.0

1.2

Figure 3.14 – Ambient Temperature Correction of the Overload Stage T>


Example of a Behavior of the Thermal Model

Figure 3.15 shows an example of the thermal model behavior. In
this example

τ = 30 minutes, k = 1.06 and kτ = 1 and the current has

been zero for a long time and thus the initial temperature rise is 0 %.
At time = 50 minutes the current changes to 0.85xI

N

and the tempera-

ture rise starts to approach value (0.85/1.06)

2

= 64 % according the

time constant. At time=300 min, the temperature is about stable, and
the current increases to 5 % over the maximum defined by the rated
current and the service factor k. The temperature rise starts to
approach value 110 %. At about 340 minutes the temperature rise is
100 % and a trip follows.

Initial Temperature Rise After Restart

When the relay is switched on, an initial temperature rise of
70 % is used. Depending of the actual current, the calculated
temperature rise then starts to approach the final value.

Alarm

Function

The thermal overload stage is provided with a separately settable
alarm function. When the alarm limit is reached the stage activates
its start signal.