Rockwell Automation 865 Differential Protection Relay User Manual

Page 38

Advertising
background image



2-26

Local Panel User Interface

865-UM001A-EN-P – July 2009

TRANSFORMER

SETTING

Rated voltage in IL side (typically high voltage side)

Rated voltage in I’L side (typically low voltage side)

Rated power of transformer

Connection group of transformer

Zero current compensation in IL side (If transformer is earthed in
IL side, this must set as “ON”)

Zero current compensation in I’L side (If transformer is earthed
in I’L side, this must set as “ON”)

Connection group of the unit transformer, if any. IEC marking
with capital letters Y and D for HV side and small case letters y
and d for LV side combined with the dial hour is used. For
example Yd11 means a wye-delta transformer where the delta
side phase-to-ground voltages are leading 30

° the wye side

phase-to-ground voltages.

DEVICE INFO

Relay type (Type ALLEN BRADLEY 865)

Serial number (SerN)

Software version (PrgVer)

Bootcode version (BootVer)

DATE/TIME

SETUP

Day, month and year (Date)

Time of day (Time)

Date format (Style). The choices are "yyyy-mm-dd",
"dd.nn.yyyy" and "mm/dd/yyyy".

CLOCK

SYNCHRONISATION

Digital input for minute sync pulse (SyncDI). If any digital input
is not used for synchronization, select "".

Daylight saving time for NTP synchronization (DST).

Detected source of synchronization (SyScr).

Synchronization message counter (MsgCnt).

Latest synchronization deviation (Dev).


The following parameters are visible only when the access level is
higher than "User".

Offset, i.e. constant error, of the synchronization source (SyOS).

Auto adjust interval (AAIntv).

Average drift direction (AvDrft): "Lead" or "lag".

Average synchronization deviation (FilDev).

Configuration and
Parameter Setting
(cont.)