Recorded values of the latest eight faults – Rockwell Automation 865 Differential Protection Relay User Manual

Page 76

Advertising
background image



3-32 Protection

Functions

865-UM001A-EN-P – July 2009

Table 3.19 – Parameters of the Programmable Stages PrgN (99)

Parameter

Value

Unit

Description

Note

Status -

Blocked
Start
Trip

Current status of the stage


F
F

SCntr

Cumulative start counter

C

TCntr

Cumulative

trip

counter

C

SetGrp

1 or 2

Active setting group

Set

SGrpDI


-
DIx
VIx
LEDx
VOx

Digital signal to select the active
setting group
None
Digital input
Virtual input
LED indicator signal
Virtual output

Set

Force Off

On

Force flag for status forcing for test
purposes. This is a common flag for
all stages and output relays, too.
Automatically reset by a 5-minute
timeout.

Set

Link (See

table

above)

Name for the supervised signal

Set

(See table
above)

Value of the supervised signal

Cmp

>
<

Mode of comparison
Over protection
Under protection

Set

Pickup

Pick up value scaled to primary level

Pickup

pu

Pick up setting in pu

Set

t

s

Definite operation time.

Set

Hyster

%

Dead

band

setting

Set

NoCmp

pu

Minimum value to start under
comparison. (Mode='<')

Set

Set = An editable parameter (password needed)

C = Can be cleared to zero

F = Editable when force flag is on

Recorded values of the latest eight faults

Detailed information is available on the eight latest faults: Time
stamp, fault value and elapsed delay.

Table 3.20 – Recorded Values of the Programmable Stages PrgN (99)

Parameter

Value

Unit

Description

yyyy-mm-dd

Time stamp of the recording, date

hh:mm:ss.ms

Time stamp, time of day

Flt

pu

Fault

value

EDly

%

Elapsed time of the operating time setting.
100% = trip

SetGrp 1

2

Active setting group during fault