Rockwell Automation 865 Differential Protection Relay User Manual

Page 23

Advertising
background image



Local Panel User Interface

2-11

865-UM001A-EN-P – July 2009

T

HIRD MENU OF

I>>

50/51

STAGE

I>> LOG

50/51

2006-09-14

12:25:10.288
Type
Flt
Load
EDly

1-2

2.86xIgn
0.99xIgn

81%

ExDI
ExDO
Prot

CBWE
OBJ

I>>

FAULT LOG 1

SetGrp

1


Figure 2.10 – Third and Last Menu (next to the right) of I>>50/51 Stage



This is the menu for registered values by the I>> stage. Fault logs are
explained under “Fault Logs” on page 2-13.

FAULT LOG 1 – This is the latest of the eight available logs.
You may move between the logs by pressing push buttons
ENTER and then RIGHT or LEFT.

2006-09-14 – Date of the log.

12:25:10.288 – Time of the log

Type 1-2 – The overcurrent fault has been detected in phases L1
and L2 (A & B, red & yellow, R&S, u&v).

Flt 2.86xIn – The fault current has been 2.86 per unit.

Load 0.99xIn – The average load current before the fault has
been 0.99 pu.

EDly 81% – The elapsed operation delay has been 81% of the
setting 0.60 s = 0.49 s. Any registered elapsed delay less than
100 % means that the stage has not tripped, because the fault
duration has been shorter than the delay setting.

SetGrp 1 – The setting group has been 1. This line can be
reached by pressing ENTER and several times the DOWN
button.