7-6 Communications

865-UM001A-EN-P – July 2009

Extension Port X4

This is a non-isolated RS-485 port for external I/O devices. The port
is located in the same rear panel D9S connector X4 as the local port,
but pins (7, 8, 5) are used instead of the standard RS-232 pins (2, 3,
5) used by the local port. See Figure 7.1.

Table 7.4 – Extension Port X4 Parameters

Parameter

Value

Unit

Description

Note

Protocol


None

SPA-bus
ProfibusDP
ModbusSla
ModbusTCPs
IEC-103
ExternalIO

DNP3

Protocol selection for the extension
port.
Command line interface for
SetPointPS
SPA-bus (slave)
Profibus DB (slave)
Modbus RTU slave
Modbus TCP slave
IEC-60870-5-103 (slave)
Modbus RTU master for external
I/O-modules
DNP 3.0

Set

Msg# 0

...

2

32

–1

Message counter since the device
has restarted or since last clearing

Clr

Errors 0

...

2

16

–1

Protocol errors since the device has
restarted or since last clearing

Clr

Tout 0

...

2

16

–1

Timeout errors since the device has
restarted or since last clearing

Clr




speed/DPS

Default =
38400/8N1 for
SetPointPS

Display of actual communication
parameters.
speed = bit/s
D = number of data bits
P = parity: none, even, odd
S = number of stop bits

Set = An editable parameter (password needed)

Clr = Clearing to zero is possible

The communication parameters are set in the protocol specific menus. For the local port

command line interface the parameters are set in configuration menu.