Recorded values of the latest eight faults, Earth fault protection (50n/51n), Earth fault protection i – Rockwell Automation 865 Differential Protection Relay User Manual

Page 61: 50n/51n)

Advertising
background image



Protection Functions

3-17

865-UM001A-EN-P – July 2009

Recorded Values of the Latest Eight Faults

Detailed information is available on the eight latest faults: Time
stamp, unbalance current, elapsed delay and setting group.

Table 3.10 – Parameters of the Current Unbalance Stage (8 latest faults) I

2

>, I’

2

> (46)

Parameter

Value

Unit

Description

yyyy-mm-dd

Time stamp of the recording, date

hh:mm:ss.ms

Time stamp, time of day

Flt

%In

Maximum

unbalance

current

EDly

%

Elapsed time of the operating time setting.
100% = trip

SetGrp

1
2

Active setting group during the fault


Undirectional earth fault protection is used for earth faults in low
impedance earthed networks. In high impedance earthed networks,
compensated networks and isolated networks undirectional earth
fault can be used as back-up protection.

The undirectional earth fault function is sensitive to the fundamental
frequency component of the residual current 3I

0

. The attenuation of

the third harmonic is more than 60 dB. Whenever this fundamental
value exceeds the user's pick-up setting of a particular stage, this
stage picks up and a start signal is issued. If the fault situation
remains on longer than the user's operation time delay setting, a trip
signal is issued.

Figure 3.12 – Typical block diagram of the earth fault stage I

0

>

Figure 3.13 – Typical block diagram of the earth fault stages I

0

>>, I

0

>>> and I

0

>>>>

Earth fault protection

I

0

> (50N/51N)