Recorded values of the latest eight faults – Rockwell Automation 865 Differential Protection Relay User Manual

Page 71

Advertising
background image



Protection Functions

3-27

865-UM001A-EN-P – July 2009



If this time is longer than the operating time of the CBFP stage, the
CBFP stage activates another output relay, which will remain
activated until the primary trip relay resets.


The CBFP stage is supervising all the protection stages using the
same selected trip relay, since it supervises the control signal of this
relay. See Chapter 5 for details about the output matrix and the trip
relays.

Table 3.15 – Parameters of the Circuit Breaker Failure Stage CBFP (50BF)

Parameter

Value

Unit

Description

Note

Status -

Blocked
Start
Trip

Current status of the stage


F
F

SCntr

Cumulative start counter

C

TCntr

Cumulative

trip

counter

C

Force Off

On

Force flag for status forcing for test
purposes. This is a common flag
for all stages and output relays, too.
Automatically reset by a 5-minute
timeout.

Set

CBrelay

1
2

The supervised output relay
Relay T1
Relay T2

Set

t>

s

Definite operation time.

Set

For details of setting ranges see “Protection Stages” in Chapter 10.

Set = An editable parameter (password needed)

C = Can be cleared to zero

F = Editable when force flag is on

This setting is also used by the circuit breaker condition monitoring. See Chapter 3.

Recorded Values of the Latest Eight Faults


Detailed information is available on the eight latest faults: Time
stamp and elapsed delay.

Table 3.16 – Recorded values of the Circuit Breaker Failure Stage
(8 latest faults) CBFP (50BF)

Parameter

Value

Unit

Description

yyyy-mm-dd

Time stamp of the recording, date

hh:mm:ss.ms

Time stamp, time of day

EDly

%

Elapsed time of the operating time setting.
100% = trip