Optional inbuilt ethernet port, Optional 61850 interface – Rockwell Automation 865 Differential Protection Relay User Manual

Page 133

Advertising
background image



Communications

7-7

865-UM001A-EN-P – July 2009

Optional Inbuilt Ethernet Port

This is an optional inbuilt Ethernet port for SetPointPS and Modbus
TCP and other communication protocols using TCP/IP. See Figure 7.1

The IP address, net mask, gateway, name server and NTP server are
common with the internal Ethernet port setting in section “IEC
60870-5-l01”, page 7.15.

Table 7.5 – Optional Inbuilt Ethernet Port Parameters

Parameter

Value

Unit

Description

Note

Protocol


None

SPA-bus
ModbusTCPs
IEC-103
ExternalIO

DNP3

Protocol selection for the extension
port.
Command line interface for
SetPointPS
SPA-bus (slave)
Modbus TCP slave
IEC-60870-5-103 (slave)
Modbus RTU master for external
I/O-modules
DNP 3.0

Set

Port

Default = 502

TCP/IP port.

Set

IpAddr

n.n.n.n

IP address. (Use SetPointPS to
edit.)

Set

NetMsk

n.n.n.n

Net mask (Use SetPointPS to edit.)

Set

Gatew

n.n.n.n

Gateway (Use SetPointPS to edit.)

Set

NTPSvr

n.n.n.n

IP address for network time protocol
(NTPS) server. (Use SetPointPS to
edit.)

Set

VSport

Default=23

SetPointPS port for IP

Set

Msg# 0

...

2

32

–1

Message counter since the device
has restarted or since last clearing

Clr

Errors 0

...

2

16

–1

Errors since the device has restarted
or since last clearing

Clr

Tout 0

...

2

16

–1

Timeout errors since the device has
restarted or since last clearing

Clr

Set = An editable parameter (password needed)

Clr = Clearing to zero is possible

Optional 61850 interface

With this option the relay has two communication connectors in
the rear panel : RJ-45 connector (61850 interface, Ethernet
10/100-Base T) and a 6-pin connector (Extension port).