Rockwell Automation 865 Differential Protection Relay User Manual

Page 164

Advertising
background image

9-4 Connections

865-UM001A-EN-P – July 2009

Terminal X3

No: Symbol

Description

1

+48V

Internal wetting voltage for digital inputs 1 – 6

2

DI1

Digital input 1

3

DI2

Digital input 2

4

DI3

Digital input 3

5

DI4

Digital input 4

6

DI5

Digital input 5

7

DI6

Digital input 6

8 --

--

9

A1 COM

Alarm relay 1, common connector

10

A1 NO

Alarm relay 1, normal open connector

11

A1 NC

Alarm relay 1, normal closed connector

12

T2

Trip relay 2

13

T2

Trip relay 2

14

T1

Trip relay 1

15

T1

Trip relay 1

16 --

--

17 Uaux

Auxiliary

voltage

18 Uaux

Auxiliary

voltage

Terminal X6 with optional Arc Protection

No: Symbol Description

1

BI

External arc light input

2 BO

Arc

output

3

COM

Common for BI and BO

4

S1>+

Arc sensor 1, positive connector

5

S1>

Arc sensor 1, negative connector

6

S2>+

Arc sensor 2, positive connector

7

S2>

Arc sensor 2, negative connector

Arc sensor itself is polarity free

Terminal X6 with DI19/DI20 option

No: Symbol Description
1

DI19

Digital input 19

2

DI19

Digital input 19

3

DI20

Digital input 20

4

DI20

Digital input 20

5 --

--

6

S1>+

Arc sensor 1, positive connector

7

S1>

Arc sensor 1, negative connector

Arc sensor itself is polarity free