Configuration and parameter setting – Rockwell Automation 865 Differential Protection Relay User Manual

Page 32

Advertising
background image



2-20

Local Panel User Interface

865-UM001A-EN-P – July 2009

The minimum procedure to configure a relay is:

1. Open the access level "Configurator". The default password for

configurator access level is 2.

2. Set the rated values in menu [CONF] including at least current

transformers and a protected transformer rating. Also the date
and time settings are in this same main menu.

3. Enable the needed protection functions and disable the rest of the

protection functions in main menu [Prot].

4. Set the setting parameter of the enable protection stages

according the application.

5. Connect the output relays to the start and trip signals of the

enabled protection stages using the output matrix. This can be
done in main menu [DO], although the SetPointPS program is
recommended for output matrix editing.

6. Configure the needed digital inputs in main menu [DI].

7. Configure blocking and interlockings for protection stages using

the block matrix. This can be done in main menu [Prot], although
SetPointPS is recommended for block matrix editing.


Some of the parameters can only be changed via the RS-232
serial port using the SetPointPS software. Such parameters, (for
example passwords, blockings and mimic configuration) are
normally set only during commissioning.


Some of the parameters require the restarting of the relay. This
restarting is done automatically when necessary. If a parameter
change requires restarting, the display will show as Figure 2.19.

Figure 2.19 – Example of Auto-Reset Display


Press CANCEL to return to the setting view. If a parameter must
be changed, press

the ENTER key again. The parameter can now

be set. When the parameter change is confirmed with the
ENTER key, a [RESTART]- text appears to the top-right corner
of the display. This means that auto-resetting is pending. If no
key is pressed, the auto-reset will be executed within few seconds.

Configuration and
Parameter Setting