Chapter 5 – measurement functions, Measurement accuracy, Measurement functions – Rockwell Automation 865 Differential Protection Relay User Manual

Page 111: Chapter

Advertising
background image

Chapter

5

865-UM001A-EN-P – July 2009




Measurement

Functions


All the direct measurements are based on fundamental frequency
values. (The exceptions are frequency and instantaneous current
for arc protection.) The figure shows a current waveform and the
corresponding fundamental frequency component, second
harmonic and rms value in a special case, when the current
deviates significantly from a pure sine wave.

0.00

0.05

0.10

0.15

0.20

0.25

0.30

Time (s)

Curr

ent

(PU)

-10

-5

0

5

10

rms

IL2

f1

f2

Load = 0%

InrushCurrentLoad0

Relative

2nd

harmonic

f2/f1

(%)

0

50

100

f2/f1 (%)

Figure 5.1 – Example of various current values of a transformer inrush current

Table 5.1 – Phase Current Inputs I

L1

, I

L2

, I

L3

, I’

L1

, I’

L2

, I’

L3

Measuring range

0 – 250 A (5A)
0 – 50 A (1A)

Inaccuracy

I

≤ 7.5 A

0.5 % of value or 15 mA

I > 7.5 A

3 % of value

The rated input I

N

is 5A or 1A. It is specified in the order code of the

relay. The specified frequency range is 45 Hz – 65 Hz.

Table 5.2 – Residual Current Inputs I

01

, I

02

Measuring range

0 – 5 xI

n

Inaccuracy I

≤ 1.5 xI

n

0.3 % of value or 0.2 % of I

n

I > 1.5 xI

n

3 % of value

The specified frequency range is 45 Hz – 65 Hz.

The rated input I

n

is 5A or 1A. This must be specified when ordering

the relay.

Measurement Accuracy

Advertising