Settings for read-only objects, Controlling with di, Local/remote selection – Rockwell Automation 865 Differential Protection Relay User Manual

Page 125

Advertising
background image



Control Functions

6-7

865-UM001A-EN-P – July 2009

Settings for Read-only Objects

Each read-only object has the following settings:

Table 6.9 – Settings for Read-only Objects

Setting

Value

Description

DI for ‘obj open’

Open information

DI for ‘obj close’

None, any digital input, virtual

input or virtual output

Close information

Object timeout

0.02 … 600 s

Timeout for state changes


If changing states takes longer than the time defined by “Object
timeout” setting, object fails and “Object failure” matrix signal is set.
Also undefined-event is generated.

Controlling with DI

Objects can be controlled with digital input, virtual input or virtual
output. There are four settings for each controllable object:

Table 6.10 – Controlling with DI

Setting

Active

DI for remote open control

DI for remote close control

In remote state

DI for local open control

DI for local close control

In local state


If the device is in local control state, the remote control inputs are
ignored and vice versa. Object is controlled when a rising edge is
detected from the selected input. Length of digital input pulse should
be at least 60 ms.

Local/Remote

Selection

In Local mode, the output relays can be controlled via a local HMI,
but they cannot be controlled via a remote serial communication
interface.

In Remote mode, the output relays cannot be controlled via a local
HMI, but they can be controlled via a remote serial communication
interface.

The selection of the Local/Remote mode is done by using a local
HMI, or via one selectable digital input. The digital input is
normally used to change a whole station to a local or remote mode.
The selection of the L/R digital input is done in the “Objects” menu
of the SetPointPS software.

NOTE:

A password is not required for a remote control operation.