Measurement Functions

5-5

865-UM001A-EN-P – July 2009


For residual currents to inputs I

01

or I

02

use the corresponding

CT

PRI

and CT

SEC

values. For earth fault stages using I

0Calc

signals

use the phase current CT values for CT

PRI

and CT

SEC

.

Example

1: Secondary to primary.

CT = 500/5

Current to the relay's input is 4 A.

⇒ Primary current is I

PRI

= 4x500/5 = 400 A

Example

2: Primary to secondary.

CT = 500/5

The relay displays I

PRI

= 400 A

⇒ Injected current is I

SEC

= 400x5/500 = 4 A

Per unit [pu] scaling

For phase currents excluding ArcI> stage
1 pu = 1xI

N

= 100 %, where

I

N

is the rated current of the transformer.

The rated current for high voltage side (HV) and low voltages side
(LV) are calculated by the device itself using Equation 4.1.

Equation

5.1

N

N

N

U

S

I

=

3

Where

I

N

=

The rated current 1 pu.

S

N

=

Rated apparent power of the protected device

U

N

=

Rated line-to-line voltage of the protected device

For residual currents and ArcI> stage
1 pu = 1xCT

SEC

for secondary side and

1 pu = 1xCT

PRI

for primary side.

Table 5.11 – Phase Current Scaling / Residual Current Scaling

Phase current scaling excluding
ArcI> stage

Residual current (3I

0

) scaling and

phase current scaling for ArcI> stage

secondary

⇒ per unit

N

SEC

PRI

SEC

PU

I

CT

CT

I

I

=

SEC

SEC

PU

CT

I

I

=

per unit

⇒ secondary

PRI

N

SEC

PU

SEC

CT

I

CT

I

I

=

SEC

PU

SEC

CT

I

I

=