Virtual inputs and outputs – Rockwell Automation 865 Differential Protection Relay User Manual

Page 121

Advertising
background image



Control Functions

6-3

865-UM001A-EN-P – July 2009

Table 6.4 – Summary of Digital Inputs

DI Terminal

Operating

voltage

Availability

X3:1

48V

DC

supply for DI1…6

1

X3:2

2

X3:3

3

X3:4

4

X3:5

5

X3:6

6

X3:7

Internal 48V

DC

Allen-Bradley 865

19

X6:1…2

External 18…865 V

DC

50…250 V

AC

ARC card with 2 DIs

Virtual Inputs and Outputs

There are four virtual inputs and six virtual outputs. The four virtual
inputs acts like normal digital inputs. The state of the virtual input
can be changed from display, communication bus and from
SetPointPS. For example setting groups can be changed using virtual
inputs.

Table 6.5 – Parameters of Virtual Inputs

Parameter

Value

Unit

Description

Set

VI1 ... VI4

0
1

Status of virtual input

Events On

Off

Event

enabling

Set

NAMES for VIRTUAL INPUTS (editable with SetPointPS only)

Label String

of

max.

10 characters

Short name for VIs on the
local display
Default is "VIn", n=1...4

Set

Description String

of

max.

32 characters

Long name for VIs. Default is
"Virtual input n", n=1...4

Set

Set = An editable parameter (password needed)

The six virtual outputs do act like output relays, but there are no
physical contacts. Virtual outputs are shown in the output matrix and
the block matrix. Virtual outputs can be used with the user's
programmable logic and to change the active setting group etc.