Circuit-breaker failure protection (50bf), Circuit-breaker failure protection cbfp (50bf) – Rockwell Automation 865 Differential Protection Relay User Manual

Page 70

Advertising
background image



3-26 Protection

Functions

865-UM001A-EN-P – July 2009

Table 3.14 – Parameters of the Thermal Overload Stage T> (49)

Parameter

Value

Unit

Description

Note

Status -

Blocked
Start
Trip

Current status of the stage


F
F

Time

hh:mm:ss

Estimated time to trip

SCntr

Cumulative start counter

C

TCntr

Cumulative

trip

counter

C

Force Off

On

Force flag for status forcing for test
purposes. This is a common flag for
all stages and output relays, too.
Automatically reset by a 5-minute
timeout.

Set

T

%

Calculated temperature rise. Trip
limit is 100 %.

F

MaxRMS

Arms

Measured current. Highest of the
three phases.

Imax

A

kxIgn. Current corresponding to the
100 % temperature rise.

k>

xIn

Allowed overload (service factor)

Set

Alarm

%

Alarm

level

Set

tau

min

Thermal time constant

Set

ctau

xtau

Coefficient for cooling time constant.
Default = 1.0

Set

kTamb

xIn

Ambient temperature corrected max.
allowed continuous current

Imax40

%In

Allowed load at Tamb +40

°C.

Default = 100 %.

Set

Imax70

%In

Allowed load at Tamb +70

°C.

Set

Tamb

°C

Ambient temperature. Editable
Samb=n/a. Default = +40

°C

Set

Samb

n/a
ExtAI1...16



Sensor for ambient temperature
No sensor in use for Tamb
External Analogue input 1...16

Set

For details of setting ranges see “Protection Stages” in Chapter 10.

Set = An editable parameter (password needed)

C = Can be cleared to zero

F = Editable when force flag is on

The circuit breaker failure protection can be used to trip any upstream
circuit breaker (CB), if the fault has not disappeared within a given
time after the initial trip command. A different output contact of the
relay must be used for this backup trip.


The operation of the circuit-breaker failure protection (CBFP) is
based on the supervision of the signal to the selected trip relay and
the time the fault remains on after the trip command.

Circuit-breaker failure

protection CBFP (50BF)

Advertising