Chapter 5

Connecting the Kinetix 6000 Drive System

This example applies to a common-bus follower IAM module.

Figure 50 - IAM Module (IPD connector)

Table 64 - Input Power (IPD) Connections

Table 65 - Termination Specifications

ATTENTION: Make sure the common-bus power connections are correct when
wiring the IPD connector plug and that the plug is fully engaged in the module
connector. Incorrect wiring/polarity or loose wiring can cause explosion or
damage to equipment.

DC-

DC+

L3

L2

L1

1 2 3 4 5 6

Kinetix 6000
IAM Module, Top View

IPD Connector
(IAM or follower IAM module)

IPD Pin

Signal

6

N.C.

5

N.C.

4

N.C.

3

2

DC+

1

DC-

IMPORTANT

Do not connect three-phase input power to the common-bus follower IAM
module.

IAM Module Cat. No.

Input VAC

Recommended
Wire Size
mm

2

(AWG)

Strip Length
mm (in.)

Torque Value
N•m (lb•in)

2094-AC05-Mxx-x

230V AC

2.5 (14)

10 (0.38)

0.5…0.6
(4.4…5.3)

2094-AC09-M02-x

4.0 (12)

2094-AC16-M03-x

10 (8)

16 (0.63)

2.4…3.0
(21.6…26.5)

2094-AC32-M05-x

30 (3)

2094-BC01-Mxx-x
2094-BC02-M02-x

460V AC

2.5 (14)

10 (0.38)

1.2…1.5
(10.6…13.2)

2094-BC04-M03-x

6 (10)

16 (0.63)

2.4…3.0
(21.6…26.5)

2094-BC07-M05-x

30 (3)