Rockwell Automation Publication 2094-UM001H-EN-P - June 2013

135

Configure and Start the Kinetix 6000 Drive System

Chapter 6

4. Set the sercos communication rate with DIP switches 2 and 3.

5. Set the sercos optical power level to High with DIP switch 1.

6. Repeat

step 4

and

step 5

for each 2094-

xMxx-x AM module.

IMPORTANT

When two or more IAM modules are connected to the same sercos
interface module, each node address must be unique.

Refer to the node addressing examples beginning on

page 136

.

For This Communication Rate

Set Switch 2

Set Switch 3

4 Mbps

OFF

ON

8 Mbps

(1)

(1) The Kinetix 6000M IDM system supports only 8 Mbps and is hardwired for this setting.

ON

OFF

For This Optical Power Level

Set Switch 1

Low

OFF

High

ON

Note: Switch numbers as seen on the IAM

are upside down in this orientation.

Switch numbers shown above are
turned around for clarity.

1

2

3

1

2

3

DIP Switches Set for

4 Mbps Applications

(high power setting)

DIP Switches Set for

8 Mbps Applications

(high power setting)

ON

OFF

Sercos Communication Rate
and Optical Power Switches

Kinetix 6000 IAM/AM Module,
(AM module is shown)

ON

OFF

Switch in ON Position

Switch in OFF Position