Upgrading the Drive Firmware

The Progress dialog box opens and
upgrading begins.

The drive module seven-segment
status indicator changes from the fixed 2, 3, or 4 to F, which indicates that
upgrading is in progress.

After the upgrade information is
sent to the drive, the drive resets
and performs diagnostic checking.

14. Wait for the Progress dialog box to

time out.

15. The Update Status dialog box opens and indicates success or failure as

described below.

16. Click OK.

Upgrading Status

If

Success

1. Update complete appears in a GREEN Status dialog box.
2. Go to

step 16

.

Failure

1. Update failure appears in a RED Status dialog box.
2. Refer to ControlFLASH Firmware Upgrade Kit Quick Start, publication

1756-QS105

, for troubleshooting information.