84

Rockwell Automation Publication 2094-UM001H-EN-P - June 2013

Chapter 5

Connecting the Kinetix 6000 Drive System

Figure 40 - Grounded (B-Phase) Power Configuration (Delta Secondary)

The IAM module has a factory-installed ground jumper configured for grounded
power distribution.

Refer to Appendix A on

page 187

, for input-power interconnect diagrams with

and without the LIM module.

L3

L1

L2

DC-

DC+

L3

L2

L1

CONT EN-

CONT EN+

W

V

U

MBRK -

MBRK +

COM

PWR

DBRK -

DBRK +

CTRL 2

CTRL 1

1 2 3 4

1 2 3 4 5 6

1 2

1 2 3 4 5 6

1 2

BAUD

RATE

TX

RX

DPI

1 2 3 4 5 6 7 8 9

Transformer (Delta) Secondary

Bonded Cabinet

Ground

Transformer

Ground Grid or

Power Distribution Ground

Kinetix 6000 IAM Module,

Top View

Connect to power rail ground stud.

Three-phase

AC Line Filter

Input Fusing

M1

Contactor

IMPORTANT

If you determine that you have grounded power distribution in your plant, you
do not need to modify your IAM module.