Rockwell Automation Publication 2094-UM001H-EN-P - June 2013

41

Planning the Kinetix 6000 Drive System Installation

Chapter 2

Observe these guidelines when the 2094-AL09 or 2094-BL02 LIM module is
used in the Bulletin 2094 system and mounted left of the IAM module:

The clean zone (C) is to the right and beneath the Bulletin 2094 system

(gray wireway).

The dirty zone (D) is to the left and above the Bulletin 2094 system, and

above and below the LIM module (black wireway).

The very dirty zone (VD) is limited to where the LIM module VAC

output jumpers over to the IAM module. Shielded cable is required only if
the very dirty cables enter a wireway.

The sercos fiber-optic cables are immune to electrical noise, but due to

their delicate nature, route them in the clean zone.

This layout is preferred due to the reduced size of the very dirty zone.

Figure 14 - Noise Zones (LIM mounted left of IAM module)

(1) If drive system I/O cable contains (dirty) relay wires, route cable with LIM module I/O cable in dirty wireway.
(2) When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples, refer to the

System Design for Control of Electrical Noise Reference Manual, publication

GMC-RM001

.

(1)

C

D

D

D

D

VD

C

D

C

Line Interface Module

Kinetix 6000
System

Dirty Wireway

Clean Wireway

I/O

(1)

and Feedback Cables

Motor Power Cables

Very Dirty Filter/IAM Connections

Segregated (not in wireway)

Route 24V DC I/O
shielded cable.

Route encoder/analog/registration

shielded cables.

Fiber-optic Cable

No sensitive

(2)

equipment within

150 mm (6.0 in.).