Upgrade drive firmware with controlflash software, Before you begin – Rockwell Automation 2094-xMxx-S Kinetix 6000 Multi-axis Servo Drives User Manual User Manual

Page 216

Advertising
background image

216

Rockwell Automation Publication 2094-UM001H-EN-P - June 2013

Appendix B

Upgrading the Drive Firmware

Upgrade Drive Firmware
with ControlFLASH Software

Upgrading axis module firmware by using ControlFLASH software involves
configuring your controller communication, selecting the drive to upgrade, and
upgrading the firmware.

Before You Begin

You need the following software and information before you begin.

Description

Cat. No.

Firmware Revision or
Software Version

RSLogix 5000

software or

the Logix Designer application

RSLogix 5000

software

15.x or later

Logix Designer application

21.x or later

ControlLogix sercos module

1756-MxxSE

15.32 or later

1756-L60M03SE

15.4 or later

CompactLogix sercos module

1768-M04SE

15.35 or later

SoftLogix sercos PCI card

1784-PM16SE

15.33 or later

RSLinx® software

2.50 or later

ControlFLASH software kit

(1)

(1) Download the ControlFLASH kit from

http://support.rockwellautomation.com/controlflash

. Contact Rockwell Automation Technical

Support at (440) 646-5800 for assistance.
For more ControlFLASH information (not drive specific), refer to the ControlFLASH Firmware Upgrade Kit User Manual, publication

1756-UM105

.

4.00.09 or later

Catalog number of the targeted IAM/AM module you want to upgrade

Network path to the targeted IAM/AM module.

IMPORTANT

Control power must be present at CPD-1 and CPD-2 prior to upgrading your
target drive.

The seven-segment status indicator on the target IAM (inverter) module or AM
module must be displaying a fixed 2, 3, or 4 before beginning this procedure.

ATTENTION: To avoid personal injury or damage to equipment during the
firmware upgrade due to unpredictable motor activity, do not apply three-
phase AC or common-bus DC input power to the drive.