Rockwell Automation Publication 2094-UM001H-EN-P - June 2013

53

Mounting the Kinetix 6000 Drive System

Chapter 3

Figure 22 - Module Mounting Order Example

Highest Power Utilization

Lowest Power Utilization

Integrated Axis Module

2094-BC02-M02-x

IPIM Module

2094-SEPM-B24-S

Axis Module

2094-BM02-x

Axis Module

2094-BM02-x

Axis Module

2094-BM01-x

Axis Module

2094-BM01-x

Shunt Module

2094-BSP2

Slot-filler Module

2094-PRF

IMPORTANT

The IAM module must be positioned in the leftmost slot of the power rail.
Position your AM/IPIM modules, shunt module, and slot-filler modules to the
right of the IAM module.

The shunt module must be installed to the right of the last AM/IPIM module.
Only slot-filler modules can be installed to the right of the shunt module.

Do not mount the shunt module on power rails with a follower IAM module.
Common-bus follower IAM modules disable the internal, rail mounted, and
external shunt modules.

SHOCK HAZARD: To avoid personal injury due to electrical shock, place a
2094-PRF slot-filler module in all empty slots on the power rail. Any power rail
connector without a module installed disables the Bulletin 2094 system;
however, control power is still present.