Logix5000/drive fault behavior, Table 110 – Rockwell Automation 2094-xMxx-S Kinetix 6000 Multi-axis Servo Drives User Manual User Manual

Page 176

Advertising
background image

176

Rockwell Automation Publication 2094-UM001H-EN-P - June 2013

Chapter 7

Troubleshooting the Kinetix 6000 Drive System

Table 110 - Logix5000/Drive Fault Behavior

Logix5000 Fault Message
(HIM Message)

Error
Code

Description

Drive Fault Action/
Attribute

Logix Designer
Programmable
Fault Action?

BusUndervoltageFault

(Blown fuse)

E00

A blown fuse was detected in the inverter pcb.

Coast/Disable (open
contactor enable relay)

No

MotorOvertempFault

(Motor Overtemp)

E04

(1)

The motor thermal switch was tripped.
Firmware I

2

t protection does not generate a fault, rather it dynamically folds back

current when 110% of motor rating is reached. Setting the Motor Thermal fault
action to Status Only or Stop Motion bypasses the foldback behavior and allows the
fault to occur.

N/A

Yes
Motor Thermal

DriveOvercurrentFault

(Power Fault)

E05

An instantaneous over-current was detected in the inverter power section.

Coast/Disable (open
contactor enable relay)

No

HardOvertravelFault

(+/- Hard Overtravel)

E06

Axis moved beyond the physical travel limits in the positive/negative direction. This
fault can be configured for status only.

Decel/Disable

Yes
Hard Overtravel

MotFeedbackFault

(Motor Feedback Loss)

E07

The feedback wiring is open, shorted or missing.

Coast/Disable

No

BusUndervoltageFault

(Bus Under Voltage)

E09

With 3-phase present, the DC bus voltage is below limits. The trip point is 275V and
137V DC for 460V/230V drives respectively.

Coast/Disable (open
contactor enable relay)

No

DC bus voltage is below limits when any axis on common-bus follower power rail
was enabled.

DriveOvervoltageFault

(Bus Overvoltage)

E10

The DC bus voltage is above limits. The trip point is 820V and 410V DC for 460V/230V
drives respectively.

Coast/Disable (open
contactor enable relay)

No

MotFeedbackFault

(Illegal Hall State)

E11

State of Hall feedback inputs in incorrect.

Coast/Disable

No

SoftovertravelFault

(+/- Software Overtravel)

E16

Axis position exceeded maximum software setting in the positive/negative
direction. This fault can be configured for status only.

Decel/Disable

Yes
Soft Overtravel

OverSpeedFault

(Overspeed Fault)

E18

Axis speed has reached 150% of the maximum rated setting. The 100% trip point is
dictated by the lesser of the user velocity limits or the motor rated base speed.

Coast/Disable

No

PositionErrorFault

(Follow Error)

E19

Axis position error limit has been exceeded. This fault can be configured for status
only.

Decel/Disable

Yes
Position Error

MotFeedbackFault

(Mtr Fdbk AQB)

E20

Motor encoder has encountered an illegal state transition.

Coast/Disable

No

AuxFeedbackFault

(Aux Feedback Comm)

E21

Communication was not established with an intelligent (Stegmann) encoder on the
Auxiliary feedback port.

Decel/Disable

No

MotFeedbackFault

(Motor Feedback Comm)

E30

Communication was not established with an intelligent (Stegmann) encoder on the
Motor feedback port.

Decel/Disable

No

GroundShortFault

(Ground Fault)

E34

Excessive ground current in the converter was detected.

Coast/Disable (open
contactor enable relay)

No

DriveUndervoltageFault

(Precharge Fault)

E35

The converter pre-charge cycle has failed.

Coast/Disable (open
contactor enable relay)

No

DriveOvertempFault

(System Overtemperature)

E36

(2)

Converter internal temperature limit exceeded.

Coast/Disable (open
contactor enable relay)

No

PowerPhaseLossFault

(Phase Loss Flt)

E37

One or two phases of the input AC power are missing.

Coast/Disable (open
contactor enable relay)

No

All phases of the input AC power are missing.
Axis was enabled when main (three-phase) power was removed.
Common-bus follower axis was enabled when DC bus power was removed.

Decel/Disable