Rockwell Automation Publication 2094-UM001H-EN-P - June 2013

149

Configure and Start the Kinetix 6000 Drive System

Chapter 6

Configure Axis Properties

The peak current ratings of the Kinetix 6000 AM modules (series A, B, and C)
are configured at the factory as 150% of continuous current. You can program
460V (series B and C) AM modules and the equivalent IAM (inverter) modules,
for up to 250% of continuous inverter current.

Refer to

Appendix F

on

page 255

to recalculate torque and acceleration or

deceleration limit values, and paste them into the appropriate Axis Properties
dialog box in the Logix Designer application.

Follow these steps to configure Axis properties for motor feedback.

1. Right-click an axis in the Controller Organizer and choose Properties.

The Axis Properties dialog box opens.

2. Click the Drive/Motor tab.
3. Click Change Catalog.

The Change Catalog Number dialog box opens.

4. Select the motor catalog number appropriate for your application.

To verify the motor catalog number, refer to the motor name plate.

5. Click OK.