Configure the Load Observer Feature

When load observer and the torque low-pass filter are both enabled, and the low-
pass filter bandwidth is less than 5 times the load observer bandwidth, their
interaction can interfere with each other, causing instability. The low-pass filter is
always limited to a bandwidth under 389 Hz in drive firmware prior to revision
1.116. As a result, an IDN parameter was added in drive firmware revision 1.116
to override the torque low-pass filter bandwidth limiting. The filter is also
bypassed if the override IDN is set to one and the torque low-pass filter
bandwidth is set to zero.

Table 125 - Torque Low-pass Filter Bandwidth

Refer to

Appendix E

on

page 249

for more information on changing IDN

parameter values with read/write messages in the Logix Designer application.

IDN
P:0:065

Bandwidth in the Logix
Designer Application

Actual Bandwidth in
Drive

Drive Firmware Notes

0

= 0

389 Hz

Operation before revision
1.116

> 0

Limited to

≤ 389 Hz

1

= 0

Filter bypassed

Operation with revision
1.116 or later

> 0

Limited to

≤ 10,430 Hz