Figure 4 - Typical (400V-class) DC Common Bus System Installation

In the example above, the leader IAM module is connected to the follower IAM
module via the DC common-bus. The follower system also includes the
Kinetix 6000M integrated drive-motor (IDM) power interface module (IPIM)
that supports up to 16 IDM units.

When planning your panel layout, you must calculate the total bus capacitance of
your DC common-bus system to be sure that the leader IAM module is sized
sufficiently to pre-charge the entire system. Refer to

Appendix C

, beginning on

page 225,

for more information.

Kinetix 6000 Multi-axis Servo Drive System

Three-phase
Input Power

115/230V Control Power

2094-BCxx-Mxx-S

IAM Module

Common Bus Leader

2094-PRSx

Power Rail

2094-BMxx-S
Axis Modules (5)

2094-BSP2
Shunt Module
(optional component)

2094-PRF
Slot-filler Module
(required to fill
any unused slots)

2094-BCxx-Mxx-S

IAM Module

Common Bus Follower

2094-PRSx

Power Rail

2094-BMxx-S
Axis Modules (5)

2094-PRF
Slot-filler Module
(required to fill
any unused slots)

2094-BLxxS

Line Interface Module
(optional component)

DC Common Bus

2090-XXLF-xxxx

AC Line Filter

(required for CE)

2094-SEPM-B24-S
IPIM Module

IMPORTANT

If total bus capacitance of your system exceeds the leader IAM module pre-
charge rating and input power is applied, the IAM module seven-segment
status indicator displays error code E90 (pre-charge timeout fault).

To correct this condition, you must replace the leader IAM module with a larger
module or decrease the total bus capacitance by removing the IPIM module or
AM modules.