Chapter 2

Planning the Kinetix 6000 Drive System Installation

Observe these guidelines when the 2094-AL09 or 2094-BL02 LIM module is
used in the Bulletin 2094 system and mounted above the IAM module:

The clean zone (C) is to the right and beneath the Bulletin 2094 system

(gray wireway).

The dirty zone (D) is to the left and above the Bulletin 2094 system, and

above and below the LIM module (black wireway).

The LIM VAC output is very dirty (VD). Use shielded cable with a braid

clamp attached at both ends of the cable to reduce the rating to dirty (D).

The sercos fiber-optic cables are immune to electrical noise, but due to

their delicate nature, route them in the clean zone.

Figure 15 - Noise Zones (LIM mounted above IAM module)

(1) For examples of shield clamp attachment, refer to the System Design for Control of Electrical Noise Reference Manual, publication

GMC-RM001

.

(2) If drive system I/O cable contains (dirty) relay wires, route cable in dirty wireway.
(3) When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples, refer to the

System Design for Control of Electrical Noise Reference Manual, publication

GMC-RM001

.

VD

D

D

D

D

C

C

C

Line Interface Module

Kinetix 6000
System

Dirty Wireway

Clean Wireway

Motor Power Cables

Very dirty LIM/IAM

(1)

connections must be
shielded with braid
clamp at both ends.

I/O

(2)

and Feedback Cables

No sensitive

(3)

equipment within

150 mm (6.0 in.).

Route 24V DC I/O
shielded cable.

Route encoder/analog/registration

shielded cables.

Fiber-optic Cable