Configure and Start the Kinetix 6000 Drive System

Figure 80 - Node Addressing Example 1

In Example 1, the Kinetix 6000 (6-axis) drive system 1 power rail contains one
IAM module, three AM modules, one shunt module, and one slot-filler module.
The shunt module and slot-filler modules are not assigned a sercos node address,
but the system identifies them with a slot location.

Kinetix 6000 (2-axis) drive system 2 power rail contains one IAM module and
one AM module. The base node address of the (system 2) IAM module must be
set for an address of

≥007.

SERCOS interfaceTM

Tx (rear)

Rx (front)

OK

CP

0 1

Kinetix 6000 Drive
System 2
(2-axis power rail)

06 = Slot-filler Module slot location
05 = Shunt Module slot location
04 = AM Module (axis 4) node address
03 = AM Module (axis 3) node address
02 = AM Module (axis 2) node address
01 = IAM Module (axis 1) base node address

Logix5000 Controller
(ControlLogix controller is shown)

Sercos Fiber-optic Ring

1756-MxxSE Sercos
interface Module

08 = AM module (axis 2) node address
07 = IAM module (axis 1) base node address

Kinetix 6000 Drive

System 1 (6-axis power rail)

Receive

Receive

Transmit

Transmit

Transmit

Receive

Base Node Address

Switches

IMPORTANT

The node address for each axis module is determined by the base node-address
switch setting on the IAM module.

Do not position axis modules to the right of shunt or slot-filler modules. The
added distance between non-adjacent axes can increase electrical noise and
impedance, and requires longer fiber-optic cable lengths.

IMPORTANT

Slot-filler modules must be used to fill any unoccupied slot on the power rail.
However, you can replace slot-filler modules with AM modules or the 2094-
BSP2 shunt module (maximum one 2094-BSP2 shunt module per power rail).