Troubleshooting the Kinetix 6000 Drive System

Chapter 7

E76

DriveHardFault

(CAN Init)

DPI hardware initialization
fault detected.

Control board hardware failure.

Reset System.
If fault persists, replace system module.

E77

DriveHardFault

(Module Mismatch)

Either 230V AM module is installed on power rail with 460V IAM module, or 460V
AM module is installed on power rail with 230V IAM module.

Replace mismatched module.

E78

DriveHardFault

(Sercos Init)

Control hardware fault detected.

Cycle power.
If fault persists, replace module.

E79

DriveOvervoltage Fault

(Shunt Module Flt)

Over-temperature fault indicator on Bulletin 2094 shunt module is steady red.

Refer to Temperature Fault Status Indicator on

page 172

.

Shunt-fault indicator on Bulletin 2094 shunt module is steady red.

Refer to Shunt Fault Status Indicator on

page 172

.

Bulletin 2094 shunt module is missing from power rail.

Install missing module on power rail.
Fill empty slot with slot-filler module.

E80

DriveHardFault

(CPLD Flt)

Control hardware fault detected.

Replace module.

E81

DriveHardFault

(Common Bus Flt)

Follower IAM module detected AC input power being applied.

Remove AC input power connections from follower
IAM module.

E90

DriveHardFault

(Pre-charge Timeout Flt)

Pre-charge resistor power exceeds the resistor rating.

Wait for resistor to cool.

E95

IPIMFault

(IPIM Module Flt)

A fault has occurred in one or more IPIM modules on the power rail.

Refer to the troubleshooting chapter in the
Kinetix 6000M Integrated Drive-Motor System User
Manual, publication

2094-UM003

.

Table 99 - Seven-segment Status Indicator Error Codes (continued)

Error
Code

Fault Message - Logix
Designer
(HIM)

Anomaly or Symptom

Potential Cause

Possible Resolution