Page 147

Advertising
background image

Rockwell Automation Publication 2094-UM001H-EN-P - June 2013

147

Configure and Start the Kinetix 6000 Drive System

Chapter 6

14. From the Bus Regulator Catalog Number pull-down menu, choose the

shunt option appropriate for your actual hardware configuration.

15. Calculate additional bus capacitance, if this applies to your application,

and enter the value here (version 20.00 or later), or refer to

Appendix E

on

page 249

to set the Add Bus Cap parameter.

The Additional Bus Capacitance field applies only to the IAM module.

16. Click OK.
17. Repeat

step 1

through

step 10

for each Bulletin 2094 AM module and

each IDM unit.

If your IAM module is

And your hardware configuration includes this shunt option

Then choose

Configured as an IAM module or
common-bus leader IAM module

(1)

Internal shunt resistors only

Internal or <none>

Bulletin 2094 (rail mounted) shunt module

2094-BSP2

Bulletin 1394 passive shunt module (connected to the 2094-BSP2 shunt
module)

1394-SRxxxx

External active shunt module

Internal or <none>

Configured as a common-bus follower IAM module

(2)

N/A. Shunts are disabled on follower IAM module

CommonBus Follow

(1) Drive does not accept Internal, <none>, 2094-BSP2, or 1394-SRxxxx selection if DC bus voltage is present without having three-phase power applied.
(2) Drive does not accept CommonBus Follow selection if three-phase power or DC bus power is applied.

To avoid damage to your Bulletin 1394 external shunt module when wired to the
2094-BSP2 shunt module, verify that the proper 230V or 460V fuse is installed prior
to applying power.

Refer to Kinetix Motion Accessories Specifications Technical Data, publication

GMC-TD004

, for more information.

IMPORTANT

When configured to use the Bulletin 1394 or 2094 shunt modules, the IAM bus
regulator capacity attribute displays the utilization of total shunt power
available (as a percent) based on the power rail configuration.

Refer to Kinetix Motion Accessories Specifications Technical Data, publication

GMC-TD004

, for shunt power specification and examples.

IMPORTANT

DC common-bus applications must calculate Total Bus Capacitance and
Additional Bus Capacitance and set the Add Bus Cap parameter in the
leader IAM module. However, you can set the parameter as shown in

step 15

or by using DriveExplorer software or the Logix Designer

application, as shown in

Appendix E

.

Refer to

Appendix C

beginning on

page 225

, for more information on

making the calculations. Refer to

Appendix E

beginning on

page 249

,

for more information on setting the Add Bus Cap parameter.