Troubleshooting the Kinetix 6000 Drive System

Chapter 7

E34

GroundShortFault

(Ground Fault)

Excessive ground current in the
converter was detected.

Wiring error.

Check motor power wiring.
Check input power wiring.

Motor internal ground short.

Replace motor.

Internal malfunction.

Disconnect motor power cable from drive and
enable drive with current limit set to 0. If fault
clears, then a wiring error or motor internal
anomaly exists. If fault remains, call your sales
representative.

Grounded control power terminal
(applies to 230V systems only)

Remove ground from control power input.
Source control power from three-phase input

power (refer to page 190).

Add isolation transformer for control power.

E35

DriveUndervoltage Fault

(Pre-charge Fault)

Converter pre-charge cycle
failed.

Low AC input voltage.

Check input AC voltage on all phases.

Internal malfunction.

Call your sales representative.

E36

DriveOvertemp Fault

(System Overtemperature)

Converter thermal switch
tripped.

Excessive heat exists in the power circuitry.

Reduce acceleration rates.
Reduce duty cycle (ON/OFF) of commanded

motion.

Increase time permitted for motion.
Use larger IAM converter module.
Check for clogged vents or defective fan.
Make sure cooling is not restricted by insufficient

space around the unit.

E37

PowerPhaseLoss Fault

(Phase Loss Flt)

One or more phases of the input AC power is missing.
Axis was enabled when main (three-phase) power was removed.
common-bus follower axis was enabled when DC bus power was removed.

Check input AC voltage on all phases.
Disable axis before removing power.

E38

SercosFault

(Sercos Ring Flt)

The sercos ring is not active
after being active and
operational.

Cable disconnected.

Check that fiber-optic cable is present and
connected properly.

E39

DriveHardFault

(Self Sense Flt)

Self-sensing Commutation
Start-up Error

Motion required for self-sensing start-up
commutation was obstructed.

Verify that there are no impediments to motion

at startup, such as hard limits.

Increase self-sensing current if high friction or

load conditions exist.

Check motor or encoder wiring by using wiring

diagnostics.

E43

DriveEnableInput Fault

(Drive Enable Flt)

Missing Drive Enable Input
Signal

An attempt was made to enable the axis

through software while the Drive Enable
hardware input was inactive.

The Drive Enable input transitioned from

active to inactive while the axis was enabled.

Disable the Drive Enable Input fault.
Verify that Drive Enable hardware input is active

whenever the drive is enabled through software.

E49

DriveHardFault

(Safe-off HW Flt)

Safe torque-off function
mismatch. Drive does not
allow motion.

Loose wiring at STO connector.
Cable/header not seated properly in STO

connector.

Safe torque-off circuit missing +24V DC.

Verify wire terminations, cable/header

connections, and +24V.

Reset error and run proof test.
If error persists, return the drive to Rockwell

Automation.

E50

SercosFault

(Sercos Same ADDR)

Duplicate node address detected on sercos ring.

Verify that each sercos drive is assigned a unique
node address.

E54

DriveHardFault

(Ifbk HW Fault)

Current feedback hardware fault detected.

Replace the module

E60

DriveHardFault

(Unknown Axis)

Illegal ID bits detected

Replace the module

Table 99 - Seven-segment Status Indicator Error Codes (continued)

Error
Code

Fault Message - Logix
Designer
(HIM)

Anomaly or Symptom

Potential Cause

Possible Resolution