Appendix D

Configure the Load Observer Feature

Rigid Mechanical Loads

Follow these steps if the load is rigid or the load observer feature is being added to
a previously working set of gains with a Load Inertia Ratio > 0.

1. Calculate the Load Observer Bandwidth.

Load Observer Bandwidth: Kop = Velocity Proportional Gain

2. If the Low-pass Output Filter is enabled, verify that the Low-pass Output

Filter Bandwidth is

≥ the Velocity Proportional Gain x 2/(2pi).

3. Configure these IDN parameter values.

a. IDN P-431 = 2 (Load Observer with Velocity Estimate)

b. IDN P-432 = Kop

c. IDN P-433 = 0

d. IDN P-065 = 1

4. Refer to Compensate for High Frequency Resonances on

page 247

, to

tune-out resonant frequencies.

Compliant Mechanical Loads

Follow these steps if the load is compliant.

1. Make the following calculations:

a. Position Loop Bandwidth:

Kpp = Position Proportional Gain/(Load Inertia Ratio + 1)

b. Position Integral Bandwidth:

Kpi = Position Integral Gain/(Load Inertia Ratio + 1)

2

c. Velocity Loop Bandwidth:

Kvp = Velocity Proportional Gain/(Load Inertia Ratio + 1)

d. Velocity Integral Bandwidth:

Kvi = Velocity Integral Gain/(Load Inertia Ratio + 1)

2

e. Load Observer Bandwidth: Kop = Kvp