Chapter 2

Planning the Kinetix 6000 Drive System Installation

Keep the DC common-bus cable (very dirty) segregated from all other cables
(not in a wireway) when the 2094-AL

xxS, 2094-BLxxS, or 2094-XL75S-Cx

LIM module is used in a DC common-bus configuration and the follower IAM
module is mounted below the leader IAM module.

Figure 13 - Noise Zones (DC common bus)

(1) If drive system I/O cable contains (dirty) relay wires, route cable with LIM module I/O cable in dirty wireway.

(2) When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples, refer to the

System Design for Control of Electrical Noise Reference Manual, publication

GMC-RM001

.

C

D

VD

D

D

D

VD

D

C

VD

D

D

D

D

D

D

C

C

Line Interface Module

Kinetix 6000 System
(leader IAM)

Dirty Wireway

Clean Wireway

I/O

(1)

and Feedback Cables

Motor Power Cables

VAC Line, AUX VAC Output, 24V

VAC Line

AC Line Filter

(required for CE)

VAC Load

I/O

(1)

and Feedback Cables

Kinetix 6000 System
(follower IAM)

Very Dirty Filter/IAM Connections

Segregated (not in wireway)

Very Dirty DC Bus Connections

Segregated (not in wireway)

Route 24V DC I/O
shielded cable.

Route encoder/analog/registration

shielded cables.

Fiber-optic Cable

Fiber-optic Cable

No sensitive

(2)

equipment within

150 mm (6.0 in.).

No sensitive

(2)

equipment within

150 mm (6.0 in.).