Connecting the Kinetix 6000 Drive System
Chapter 5
Determine the Input Power
Configuration
Before wiring input power to your Kinetix 6000 system, you must determine the
type of input power you are connecting to. The IAM module is designed to
operate in both grounded and ungrounded environments.
Grounded Power Configurations
The grounded (WYE) power configuration lets you ground your three-phase
power at a neutral point. This type of grounded power configuration is preferred.
Figure 39 - Grounded Power Configuration (WYE Secondary)
Refer to
for input power
interconnect diagrams with and without the LIM module.
ATTENTION: When using a LIM module with your IAM module, the VAC LINE
input power must come from a grounded configuration (refer to
).
When not using a LIM module with your IAM module, ungrounded
configurations are permitted, but you must set the jumper to the ungrounded
position for proper drive operation.
Refer to Setting the Ground Jumper in Ungrounded Power Configurations on
for more information.
L3
L2
L1
BAUD
RATE
TX
RX
DPI
1 2 3 4 5 6 7 8 9
DC-
DC+
L3
L2
L1
CONT EN-
CONT EN+
W
V
U
MBRK -
MBRK +
COM
PWR
DBRK -
DBRK +
CTRL 2
CTRL 1
1 2 3 4
1 2 3 4 5 6
1 2
1 2 3 4 5 6
1 2
Transformer
Kinetix 6000 IAM Module,
Top View
Three-phase
Input VAC
Phase Ground
Transformer (WYE) Secondary
Bonded Cabinet
Ground
Ground Grid or
Power Distribution Ground
Connect to power rail
ground stud.
Three-phase
AC Line Filter
Input Fusing
M1
Contactor