Command Reference

2-105

Analog Output Scale

Format:

:aa04Dfddddcc<cr>

Parameter
Code:

0x04D

Valid Function
Codes:

0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x4 = Copy Non-Volatile Value to Working Value
0x5 = Copy Working Value to Non-Volatile Value
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value

Valid Exception
Codes:

0x03 = EEPROM Write Error
0x04 = Data Below Minimum
0x08 = Invalid Function Code

Data Fields:

dddd

Scaling used for the analog output. The meaning of
the scale value is dependent on the parameter
mapped to the output, as follows:

Position
Variables

Counts / Volt

Velocity
Variables

Current
Variables

Minimum
Value:

0x8001

Maximum
Value:

0x7FFF

Default:

0x0000

Value

16383

---------------- MotorMaximumSpeed

Volt

Value

8191 128

--------------------------- SysAmps