Analog output scale, Analog output scale -105 – Rockwell Automation 2098-DSD-xxx Ultra3000 Host Commands for Serial Interface User Manual
Page 121
Publication 2098-RM003A-EN-P October 2001
Command Reference
2-105
Analog Output Scale
Format:
:aa04Dfddddcc<cr>
Parameter
Code:
0x04D
Valid Function
Codes:
0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x4 = Copy Non-Volatile Value to Working Value
0x5 = Copy Working Value to Non-Volatile Value
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value
Valid Exception
Codes:
0x03 = EEPROM Write Error
0x04 = Data Below Minimum
0x08 = Invalid Function Code
Data Fields:
dddd
Scaling used for the analog output. The meaning of
the scale value is dependent on the parameter
mapped to the output, as follows:
Position
Variables
Counts / Volt
Velocity
Variables
Current
Variables
Minimum
Value:
0x8001
Maximum
Value:
0x7FFF
Default:
0x0000
Value
16383
---------------- MotorMaximumSpeed
⋅
Volt
⁄
Value
8191 128
⋅
--------------------------- SysAmps
⋅
Volt
⁄