Analog Current Offset

Analog Acceleration Limit

Format:

:aa049fddddcc<cr>

Parameter
Code:

0x049

Valid Function
Codes:

0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x4 = Copy Non-Volatile Value to Working Value
0x5 = Copy Working Value to Non-Volatile Value
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value

Valid Exception
Codes:

0x03 = EEPROM Write Error
0x04 = Data Below Minimum
0x05 = Data Above Maximum
0x08 = Invalid Function Code

Data Fields:

dddd

Analog current offset, in units of milliVolts.

Minimum
Value:

-10000

Maximum
Value:

10000

Default:

0

Format:

:aa05Dfddddddddcc<cr>

Parameter
Code:

0x05D

Valid Function
Codes:

0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x4 = Copy Non-Volatile Value to Working Value
0x5 = Copy Working Value to Non-Volatile Value
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value

Valid Exception
Codes:

0x03 = EEPROM Write Error
0x05 = Data Above Maximum
0x08 = Invalid Function Code

Data Fields:

dddddddd

Analog acceleration limit, in units of counts/sec/sec.

Minimum
Value:

0x00000000

Maximum
Value:

0x7FFFFFFF

Default:

100,000