Homing type, Homing type -55 – Rockwell Automation 2098-DSD-xxx Ultra3000 Host Commands for Serial Interface User Manual

Page 71

Advertising
background image

Publication 2098-RM003A-EN-P October 2001

Command Reference

2-55

Homing Type

Format:

:aa0C5fddcc<cr>

Parameter
Code:

0x0C5

Valid Function
Codes:

0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x4 = Copy Non-Volatile Value to Working Value
0x5 = Copy Working Value to Non-Volatile Value
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value

Valid Exception
Codes:

0x03 = EEPROM Write Error
0x05 = Data Above Maximum
0x08 = Invalid Function Code

Data Fields:

dd

Homing type code, where:
0x00: Home to sensor, forward to marker
0x01: Home to marker
0x02: Home to sensor
0x03: Home to sensor, backward to marker
0x04: Home to current setting
0x05: Home to current setting, backward to marker.

Minimum
Value:

0x00

Maximum
Value:

0x03

Default:

0x00