Publication 2098-RM003A-EN-P October 2001

2-18

Command Reference

Frame Format

Drive Address

Format:

:aa051fddcc<cr>

Parameter
Code:

0x051

Valid Function
Codes:

0x0 = Read Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value

Valid Exception
Codes:

0x03 = EEPROM Write Error
0x05 = Data Above Maximum
0x08 = Invalid Function Code

Data Fields:

dd

Frame format code, where:
0x00 7 bits, Even parity, 1 Stop
0x01: 7 bits, Odd parity, 1 Stop
0x02: 8 bits, No parity, 1 Stop
0x03: 8 bits, Even parity, 1 Stop
0x04: 8 bits, Odd parity, 1 Stop

Minimum
Value:

0x00

Maximum
Value:

0x04

Default:

0x02

Format:

:aa052fddcc<cr>

Parameter
Code:

0x052

Valid Function
Codes:

0x0 = Read Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value

Valid Exception
Codes:

0x03 = EEPROM Write Error
0x05 = Data Above Maximum
0x08 = Invalid Function Code

Data Fields:

dd

Drive address for serial communications.

Minimum
Value:

0

Maximum
Value:

253

Default:

0x00