Publication 2098-RM003A-EN-P October 2001

Command Reference

2-111

Reset Peaks

Analog Command Input

Analog Current Limit Input

Format:

:aa079fcc<cr>

Parameter
Code:

0x079

Valid Function
Codes:

0x1 = Write Working Value

Valid Exception
Codes:

0x08 = Invalid Function Code

Data Fields:

None. Resets the peak position error and peak current variables to
zero.

Format:

:aa07Afddddcc<cr>

Parameter
Code:

0x07A

Valid Function
Codes:

0x0 = Read Working Value

Valid Exception
Codes:

0x08 = Invalid Function Code

Data Fields:

dddd

A/D converter value, after scaling and offsetting, of
the analog COMMAND input, in units of mV. Ranges
from -10000 to +10000 mV.

Format:

:aa07Cfddddcc<cr>

Parameter
Code:

0x07C

Valid Function
Codes:

0x0 = Read Working Value

Valid Exception
Codes:

0x08 = Invalid Function Code

Data Fields:

dddd

A/D converter value, after scaling and offsetting, of
the analog ILIMIT input, in units of mV. Ranges from
-10000 to +10000 mV.