Home Current

Format:

:aa15Ffddddcc<cr>

Parameter
Code:

0x15F

Valid Function
Codes:

0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x4 = Copy Non-Volatile Value to Working Value
0x5 = Copy Working Value to Non-Volatile Value
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value

Valid Exception
Codes:

0x04 = Data Below Minimum
0x05 = Data Above Maximum
0x08 = Invalid Function Code

Data Fields:

dddd

Current value used when homing to a current
setting, in units of Amps*128. If the commanded
current is equal to or greater than this value, the
homing sequence is terminated or changed to
searching for a marker.

Minimum
Value:

0x0001

Maximum
Value:

0x7FFF

Default:

128