Preset velocity acceleration limit, Preset velocity deceleration limit – Rockwell Automation 2098-DSD-xxx Ultra3000 Host Commands for Serial Interface User Manual

Page 44

Advertising
background image

Publication 2098-RM003A-EN-P October 2001

2-28

Command Reference

Preset Velocity Acceleration Limit

Preset Velocity Deceleration Limit

Format:

:aa05Ffddddddddcc<cr>

Parameter
Code:

0x05F

Valid Function
Codes:

0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x4 = Copy Non-Volatile Value to Working Value
0x5 = Copy Working Value to Non-Volatile Value
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value

Valid Exception
Codes:

0x03 = EEPROM Write Error
0x05 = Data Above Maximum
0x08 = Invalid Function Code

Data Fields:

dddddddd

Preset acceleration limit, in units of counts/sec/sec.

Minimum
Value:

0x00000000

Maximum
Value:

0x7FFFFFFF

Default:

100,000

Format:

:aa060fddddddddcc<cr>

Parameter
Code:

0x060

Valid Function
Codes:

0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x4 = Copy Non-Volatile Value to Working Value
0x5 = Copy Working Value to Non-Volatile Value
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value

Valid Exception
Codes:

0x03 = EEPROM Write Error
0x05 = Data Above Maximum
0x08 = Invalid Function Code

Data Fields:

dddddddd

Preset deceleration limit, in units of counts/sec/sec.

Minimum
Value:

0x00000000

Maximum
Value:

0x7FFFFFFF

Default:

100,000